Verify main breaker + 125% solar inverter output against panelboard busbar rating and generate a combined Load Calc + PV Single-Line Diagram.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | General Lighting & Receptacles: 2,200 sq.ft. × 3 VA/sq.ft. | NEC 2023 220.82(B)(1) | 6,600 VA | 6,600 VA |
| 2 | Small Appliance & Laundry Branch Circuits: 3 circuits × 1,500 VA | NEC 2023 220.82(B)(2) | 4,500 VA | 4,500 VA |
| 3 | Fastened-in-Place Appliances (Range 10,000 + Dryer 5,000 + Water/Other 4,500 VA) | NEC 2023 220.82(B)(3)-(4) | 19,500 VA | 19,500 VA |
| 4 | Optional General Demand Factor: 100% first 10,000 VA + 40% of remaining 20,600 VA | NEC 2023 220.82 Demand | 30,600 VA | 18,240 VA |
| 5 | Largest Non-Coincident HVAC Load: Air-Conditioning / Heat Pump @ 100% | NEC 2023 220.82(C) | 4,200 VA | 4,200 VA |
| 6 | Level 2 EVSE (32A) — Continuous EVSE Load @ 125% Strict AHJ Mode | NEC 625.41 / Continuous | 7,680 VA | 9,600 VA |
| 7 | Total Calculated Dwelling Demand (32,040 VA ÷ 240V = 133.5 Amps) | NEC 2023 220.82 Total | — | 32,040 VA |
Under the NEC 705.12(B)(3)(2) 120% rule, 200A busbar u00d7 1.20 = 240A total supply rating. Subtracting the 200A main breaker leaves 40A max backfeed breaker (32A continuous inverter output) at the opposite end of the busbar, unless the main breaker is derated to 175A.