Test your existing 100A panel with a 32A, 40A, or 48A EV charger and generate a compliant EVEMS worksheet to avoid a $4,500+ 200A service upgrade.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | Living Area (135 m² + 75% of 55 m² bsmt = 176.2 m²): 5,000 W + 1 × 1,000 W | CEC 8-110 & 8-200(1)(a)(i-ii) | 176.2 m² | 6,000 W |
| 2 | Electric Range: 6,000 W base + 40% of rating exceeding 12,000 W | CEC 8-200(1)(a)(iv) | 12,000 W | 6,000 W |
| 4 | Other Loads >1,500 W (Dryer 5,400 W + Fixed 3,000 W) @ 25% (Range provided) | CEC 8-200(1)(a)(vii) | 8,400 W | 2,100 W |
| 5 | Air Conditioning / Heat Pump @ 100% (largest non-coincident w/ heating) | CEC 8-200(1)(a)(iii) & 62-118 | 3,000 W | 3,000 W |
| 6 | Grizzl-E / ChargePoint Level 2 (40A) — Monitored & Controlled by CSA-Listed EVEMS (0 W Service Demand) | CEC 8-106(10)/(11) & 8-500 | 9,600 W | 0 W |
| 7 | Total Calculated Service Demand — Greater of Item (a) 17,100 W or Min Floor (b) 24,000 W | CEC 8-200(1)(b) | Min Check | 24,000 W |
Because CEC Rule 8-200(1)(a)(vi) counts an unmanaged EV charger at 100% (11,520 W = 48A alone), pushing a typical home with an electric stove and AC past 24,000 W (100A).
By installing either a charger with native dynamic load management or a CSA-certified feeder EVEMS controller under CEC Rule 8-106(10), documented on the permit load sheet and Single-Line Diagram.