Updated for the 2026 National Electrical Code reorganization relocating Article 220 into Article 120 and lowering general lighting demand from 3 VA/ftu00b2 to 2 VA/ftu00b2.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | General Lighting & Receptacles: 2,800 sq.ft. × 2 VA/sq.ft. | NEC 2026 Art. 120(B)(1) | 5,600 VA | 5,600 VA |
| 2 | Small Appliance & Laundry Branch Circuits: 3 circuits × 1,500 VA | NEC 2026 Art. 120(B)(2) | 4,500 VA | 4,500 VA |
| 3 | Fastened-in-Place Appliances (Range 12,000 + Dryer 5,000 + Water/Other 5,000 VA) | NEC 2026 Art. 120(B)(3)-(4) | 22,000 VA | 22,000 VA |
| 4 | Optional General Demand Factor: 100% first 10,000 VA + 40% of remaining 22,100 VA | NEC 2026 Art. 120 Demand | 32,100 VA | 18,840 VA |
| 5 | Largest Non-Coincident HVAC Load: Air-Conditioning / Heat Pump @ 100% | NEC 2026 Art. 120(C) | 4,800 VA | 4,800 VA |
| 6 | Tesla Wall Connector Gen 3 (48A) — Continuous EVSE Load @ 125% Strict AHJ Mode | NEC 625.41 / Continuous | 11,520 VA | 14,400 VA |
| 7 | Total Calculated Dwelling Demand (38,040 VA ÷ 240V = 158.5 Amps) | NEC 2026 Art. 120 Total | — | 38,040 VA |
The 2026 NEC relocated load calculation rules from Article 220 to Article 120 and reduced the general lighting and receptacle unit load for dwellings from 3 VA/ftu00b2 to 2 VA/ftu00b2 to reflect modern LED lighting efficiency.