Verify if your 100A or 125A panel passes NEC Article 220 with a 32A, 40A, or 48A charger u2014 or pass inspection using a UL 916 Load Management controller.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | General Lighting & Receptacles: 1,650 sq.ft. × 3 VA/sq.ft. | NEC 220.83(A)(B)(1) | 4,950 VA | 4,950 VA |
| 2 | Small Appliance & Laundry Branch Circuits: 3 circuits × 1,500 VA | NEC 220.83(A)(B)(2) | 4,500 VA | 4,500 VA |
| 3 | Fastened-in-Place Appliances (Range 10,000 + Dryer 5,000 + Water/Other 4,500 VA) | NEC 220.83(A)(B)(3)-(4) | 19,500 VA | 19,500 VA |
| 4 | Optional General Demand Factor: 100% first 8,000 VA + 40% of remaining 20,950 VA | NEC 220.83(A) Demand | 28,950 VA | 16,380 VA |
| 5 | Largest Non-Coincident HVAC Load: Air-Conditioning / Heat Pump @ 100% | NEC 220.83(A)(C) | 3,600 VA | 3,600 VA |
| 6 | Emporia / Wallbox Level 2 (40A) — Continuous EVSE Load @ 125% Strict AHJ Mode | NEC 625.41 / Continuous | 9,600 VA | 12,000 VA |
| 7 | Total Calculated Dwelling Demand (31,980 VA ÷ 240V = 133.2 Amps) | NEC 220.83(A) Total | — | 31,980 VA |
Yes. NEC 625.42(A) and NEC 750.30 permit listed Energy Management Systems (UL 916 PCS) to monitor feeder current and dynamically curtail EVSE draw so maximum service demand never exceeds the 100A main rating.