Instant NFPA 70 dwelling load worksheet + vector Single-Line Diagram (SLD) formatted for US City & County Building Department permit portals.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | General Lighting & Receptacles: 2,400 sq.ft. × 3 VA/sq.ft. | NEC 2023 220.82(B)(1) | 7,200 VA | 7,200 VA |
| 2 | Small Appliance & Laundry Branch Circuits: 3 circuits × 1,500 VA | NEC 2023 220.82(B)(2) | 4,500 VA | 4,500 VA |
| 3 | Fastened-in-Place Appliances (Range 11,500 + Dryer 5,000 + Water/Other 5,500 VA) | NEC 2023 220.82(B)(3)-(4) | 22,000 VA | 22,000 VA |
| 4 | Optional General Demand Factor: 100% first 10,000 VA + 40% of remaining 23,700 VA | NEC 2023 220.82 Demand | 33,700 VA | 19,480 VA |
| 5 | Largest Non-Coincident HVAC Load: Central Electric Space Heating @ 65% | NEC 2023 220.82(C) | 9,600 VA | 6,240 VA |
| 6 | Tesla Wall Connector Gen 3 (48A) — Continuous EVSE Load @ 125% Strict AHJ Mode | NEC 625.41 / Continuous | 11,520 VA | 14,400 VA |
| 7 | Total Calculated Dwelling Demand (40,120 VA ÷ 240V = 167.2 Amps) | NEC 2023 220.82 Total | — | 40,120 VA |
NEC 220.82 combines general lighting (3 VA/sq.ft.), small appliance & laundry circuits (1,500 VA each), and fixed appliances, taking 100% of the first 10,000 VA plus 40% of the remainder, then adds the largest HVAC load and continuous EVSE load.
Under NEC 625.41, EV chargers are continuous loads sized at 125% of nameplate rating (e.g., 48A u00d7 240V u00d7 1.25 = 14,400 VA on a 60A 2-pole breaker), unless governed by a listed UL 916 Power Control System under NEC 625.42.