| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | Living Area (155 m² + 75% of 40 m² bsmt = 185.0 m²): 5,000 W + 2 × 1,000 W | CEC 8-110 & 8-200(1)(a)(i-ii) | 185.0 m² | 7,000 W |
| 2 | Electric Range: 6,000 W base + 40% of rating exceeding 12,000 W | CEC 8-200(1)(a)(iv) | 12,000 W | 6,000 W |
| 4 | Other Loads >1,500 W (Dryer 5,000 W + Fixed 4,500 W) @ 25% (Range provided) | CEC 8-200(1)(a)(vii) | 9,500 W | 2,375 W |
| 5 | Electric Space Heating (100% first 10 kW + 75% balance; interlocked w/ AC) | CEC 8-200(1)(a)(iii) & 62-118 | 9,000 W | 9,000 W |
| 6 | Flo Home X6 (48A CSA) — Monitored & Controlled by CSA-Listed EVEMS (0 W Service Demand) | CEC 8-106(10)/(11) & 8-500 | 11,520 W | 0 W |
| 7 | Total Calculated Service Demand — Greater of Item (a) 24,375 W or Min Floor (b) 24,000 W | CEC 8-200(1)(b) | Min Check | 24,375 W |
Yes, CSA-certified EVEMS devices installed per CEC Rule 8-106(10)/(11) and Rule 8-500 are recognized across BC to prevent unnecessary service upgrades on 100A homes.