Generate an OESC Rule 8-200 calculation schedule + Single-Line Diagram formatted for Ontario electrical notifications and LDC service upgrades.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | Living Area (195 m² + 75% of 80 m² bsmt = 255.0 m²): 5,000 W + 2 × 1,000 W | CEC 8-110 & 8-200(1)(a)(i-ii) | 255.0 m² | 7,000 W |
| 2 | Electric Range: 6,000 W base + 40% of rating exceeding 12,000 W | CEC 8-200(1)(a)(iv) | 12,000 W | 6,000 W |
| 4 | Other Loads >1,500 W (Dryer 5,500 W + Fixed 5,000 W) @ 25% (Range provided) | CEC 8-200(1)(a)(vii) | 10,500 W | 2,625 W |
| 5 | Air Conditioning / Heat Pump @ 100% (largest non-coincident w/ heating) | CEC 8-200(1)(a)(iii) & 62-118 | 4,200 W | 4,200 W |
| 6 | Tesla Wall Connector Gen 3 (48A) — Continuous EV Supply Equipment @ 100% | CEC 8-200(1)(a)(vi) | 11,520 W | 11,520 W |
| 7 | Total Calculated Service Demand — Greater of Item (a) 31,345 W or Min Floor (b) 24,000 W | CEC 8-200(1)(b) | Min Check | 31,345 W |
Yes. The Ontario Electrical Safety Code adopts CSA C22.1 Section 8 demand factors for single dwellings and secondary suites, requiring documented load calculations when adding EVSE, heat pumps, or secondary units.